Aerial Bundled Cable with IEC60502 Standard

Aerial Bundled Cable with IEC60502 Standard

Overhead Aerial Bundled Cable With XLPE Insulation

overhead single core, 2 core, 4 core Aerial Bundled Cable with XLPE insulation

Aerial-Bundled-Cable-with-IEC60502-Standard.jpg

Application

To be used at cotages of 600V phase-to-phase or less and at conductor temperatures not to exceed 75oC for polyethylene insulated conductors or 90oC for crossliked polyethylene(XLPE) insulated conductors. The assembled insulated conductor shall be suitable for use in a system having a standard operating voltage not exceeding 600/1000V. The cores of an aerial bundled conductor shall be laid-up with a left-hand lay. The length of lay shall be 55-75 times the diameter of a phase conductor.


Construction

The conductors shall be stranded circular,except where otherwise stated,shall comply with all the requirement for class 2 compacted stranded circular conductors of IEC60502.


Technical parameters:


(1)Self-supporting

PhasePhasePhaseApprox.Overall DiameterMax. D.C. Resistance of Conductor at 20℃
AAC+UV-XLPECompact ConductorUV-XLPE Insulation  
No.X No.Cross Section of CoresNo.of Al WiresOverall DiameterNormal ThicknessMin.Diameter  
No. X mm2-mmmmmmmmmmohm/km
1 X 1074.051.00.86.056.053.08
1 X 1674.81.20.987.27.201.91
1 X 25761.20.988.48.401.20
1 X 3577.01.41.169.89.800.868
1 X 5078.31.41.1611.111.100.641
1 X 70199.81.41.1612.612.600.443
1 X 951911.61.61.3414.814.800.320
1 X 12019131.61.3416.216.200.253
1 X 1501914.61.81.5218.218.200.206
1 X 1853616.22.01.7020.220.200.164
1 X 2403618.42.21.8822.822.800.125
2 X 1074.051.00.86.0512.103.08
2 X 1674.81.20.987.214.401.91
2 X 25761.20.988.416.801.20
2 X 3577.01.41.169.819.600.868
2 X 5078.31.41.1611.122.200.641
2 X 70199.81.41.1612.625.200.443
2 X 951911.61.61.3414.829.600.320
2 X 12019131.61.3416.232.400.253
2 X 1501914.61.81.5218.236.400.206
2 X 1853616.22.01.7020.240.400.164
2 X 2403618.42.21.8822.845.600.125
3 X 1074.051.00.86.0513.073.08
3 X 1674.81.20.987.215.551.91
3 X 25761.20.988.418.141.20
3 X 3577.01.41.169.821.170.868
3 X 5078.31.41.1611.123.980.641
3 X 70199.81.41.1612.627.220.443
3 X 951911.61.61.3414.831.970.320
3 X 12019131.61.3416.234.990.253
3 X 1501914.61.81.5218.239.310.206
3 X 1853616.22.01.7020.243.630.164
3 X 2403618.42.21.8822.849.250.125
4 X 1074.051.00.86.0514.643.08
4 X 1674.81.20.987.217.421.91
4 X 25761.20.988.420.331.20
4 X 3577.01.41.169.823.720.868
4 X 5078.31.41.1611.126.860.641
4 X 70199.81.41.1612.630.490.443
4 X 951911.61.61.3414.835.820.320
4 X 12019131.61.3416.239.200.253
4 X 1501914.61.81.5218.244.040.206
4 X 1853616.22.01.7020.248.880.164
4 X 2403618.42.21.8822.855.180.125

(2) Phase + Neutral

PhaseNeutralPhaseNeutralApprox.Overall DiameterMax. D.C. Resistance of Conductor at 20℃
AAC+UV-XLPEAAACCompact ConductorUV-XLPE InsulationConductor  
      PhaseNeutral
No.X No.Cross Section of CoresNo.X N.Cross Section of CoresNo.of Al.WireOverall Dia.No.ThicknessMin.No./Dia. of Al Alloy Wire   
No. X mm2No. X mm2-mm   mmMin.No./mm     mmohm/kmohm/km
1 X 161 X 1674.81.20.987/1.7012.301.912.217
1 X 251 X 25761.20.987/2.1014.701.201.393
1 X 351 X 3577.01.41.167/2.5017.300.8681.007
1 X 501 X 5078.31.41.167/3.0020.100.6410.744
1 X 701 X 70199.81.41.167/3.5023.100.4430.514
1 X 951 X 951911.61.61.3419/2.5027.300.3200.371
1 X 1201 X 12019131.61.3419/2.8030.200.2530.294
1 X 1501 X 1501914.61.81.5237/2.2533.950.2060.239
1 X 1851 X 1853616.22.01.7037/2.5037.700.1640.190
1 X 2401 X 2403618.42.21.8861/2.2543.050.1250.145
2 X 161 X 1674.81.20.987/1.7014.041.912.217
2 X 251 X 25761.20.987/2.1016.631.201.393
2 X 351 X 3577.01.41.167/2.5019.510.8681.007
2 X 501 X 5078.31.41.167/3.0022.460.6410.744
2 X 701 X 70199.81.41.167/3.5025.700.4430.514
2 X 951 X 951911.61.61.3419/2.5030.310.3200.371
2 X 1201 X 12019131.61.3419/2.8033.410.2530.294
2 X 1501 X 1501914.61.81.5237/2.2537.550.2060.239
2 X 1851 X 1853616.22.01.7037/2.5041.690.1640.190
2 X 2401 X 2403618.42.21.8861/2.2547.410.1250.145
3 X 161 X 1674.81.20.987/1.7016.151.912.217
3 X 251 X 25761.20.987/2.1019.061.201.393
3 X 351 X 3577.01.41.167/2.5022.320.8681.007
3 X 501 X 5078.31.41.167/3.0025.590.6410.744
3 X 701 X 70199.81.41.167/3.5029.220.4430.514
3 X 951 X 951911.61.61.3419/2.5034.420.3200.371
3 X 1201 X 12019131.61.3419/2.8037.870.2530.294
3 X 1501 X 1501914.61.81.5237/2.2542.560.2060.239
3 X 1851 X 1853616.22.01.7037/2.5047.250.1640.190
3 X 2401 X 2403618.42.21.8861/2.2553.630.1250.145

(3) Phase + Neutral + Service Connection

PhaseNeutralService ConnectionPhaseNeutral    Service ConnectionApprox.Overall Diameter of Bundled Cable
AAC+UV-XLPEAAAC+UV-XLPEAAC+UV-XLPEConductorUV-XLPEConductorUV-XLPECompact ConductorUV-XLPE 
No.X Normal Cross Section of CoresNo.X Normal Cross Section of CoresNo.X Normal Cross Section of CoresNo. of Al. WireOverall Dia.Normal ThicknessNo./Dia. of Al. WireNormal ThicknessNo. of Al. WireOverall Dia.Normal Thickness 
No. X mm2No. X mm2No. X mm2-mmmmmmmmNo./mmmmmmmm
3 X 161 X 501 X 1674.81.27/3.01.474.81.226.2
3 X 251 X 501 X 16761.27/3.01.474.81.228.6
3 X 351 X 501 X 1677.01.47/3.01.474.81.231.4
3 X 501 X 501 X 1678.31.47/3.01.474.81.234
3 X 701 X 501 X 16199.81.47/3.01.474.81.237
3 X 951 X 501 X 161911.61.67/3.01.474.81.241.4
3 X 1201 X 501 X 1619131.67/3.01.474.81.244.2
3 X 161 X 502 X 1674.81.27/3.01.474.81.226.2
3 X 251 X 502 X 16761.27/3.01.474.81.228.6
3 X 351 X 502 X 1677.01.47/3.01.474.81.231.4
3 X 501 X 502 X 1678.31.47/3.01.474.81.234
3 X 701 X 502 X 16199.81.47/3.01.474.81.237
3 X 951 X 502 X 161911.61.67/3.01.474.81.241.4
3 X 1201 X 502 X 1619131.67/3.01.474.81.244.2
  • Quadruplex Service Drop Wire
  • Triplex Service Drop Wire
  • Duplex Service Drop Wire
  • LV ABC Cable