12.7/22KV ABC Cable

12.7/22KV ABC Cable

12.7/22kV XLPE or HDPE insulated aerial cable

Aluminum Electrical XlPE/PVC/PE Insulated Overhead Cable LV MV Al Service Drop 12.7/22kV ABC Cable

12.7-22KV-ABC-Cable.jpg

APPLICATION:

It is preferred to use of ABC cables instead of uninsulated conductors at low voltage networks. ABC cables are especially used at areas where the cost of underground networks is expensive and also for electrification of rural areas like villages.Bundles can include one or two additional conductors for public lighting and control pair.

STANDARD:

Basic design to IEC 60502 / AS/NZS 3599-1 standards

CONSTRUCTION:

Conductor material:Aluminium

Conductor shape:Circular stranded (RM)

Material of the inner semi-conductor:Compound

Insulation:XLPE

Material of the external semi-conductor:Compound

Material of bedding:Semiconducting

Screen:Copper tape or Copper wire

Protection:separation tape

Outer sheath:HDPE

Messenger:Steel wire or AAAC, Bare or PVC/PE insulated

Dimensional characteristics

Number of cores:3

Screen section:35--240 mm²

Usage characteristics

Bending factor when laying:12 (xD)

Ambient temperature:35 °C

Minimum installation temperature:-20 °C

Max. conductor temperature in service:90 °C

Short-circuit max. conductor temperature:250 °C

Rated voltage:12.7/22kV(24kV)

Technical parameters:

PART 1 12.7/22 KV AL/XLPE /HDPE NON-SCREENED CABLES

NO.Cores X Nominal Cross SectionPhase ConductorMessenger Suspension Unit
Nominal Sectional AreaStrandingXLPE Insulation ThicknessThickness of SheathNominal Sectional AreaStrandingThickness of Sheath
No.×mm²mm²No.×mmmmmmmm²No.×mmmm
3X50 + 1X505019/1.785.51.2507/3.01.2
3X70 + 1X507019/.145.51.2507/3.151.2
3X95+ 1X509519/2.525.51.2507/3.01.2
3X185+1X12018537/2.525.51.21207/4.671.2
3X150 +1X5015037/2.255.51.2507/3.151.2
3X240 +1X5024061/2.255.51.2507/3.151.2

PART 2 12.7/22 KV AL/XLPE /CWS/HDPE SCREENED CABLES

NO.Cores X Nominal Cross SectionDiameter of ConductorCopper Wire Screen Stranding mmThickness of Sheath
No.×mm²mmlight  duty ScreenHeavy duty Screenmm
3x356.925/0.8540/0.851.8
3x508.125/0.8523/1.351.8
3x709.725/0.8532/1.351.9
3x9511.425/0.8539/1.351.9
3x12012.825/0.8539/1.352.0
3x15014.225/0.8539/1.352.0
3x18515.725/0.8539/1.352.1
  • 19/33kV ABC Overhead Cable
  • 6.35/11KV ABC Cable
  • 10KV XLPE Insulation ABC Cable