Welcome to overhead-cable.com Email: sales@zmscable.com Tel: +86 371-67829-333
AAC(All Aluminum Conductor)

AAC(All Aluminum Conductor)

AAC Conductor Bare Aluminum Conductor Cable

Overhead Bare Aluminum Conductor All Aluminum AAC Conductor AAC Cable

AAC(All-Aluminum-Conductor).jpg

Application:

AAC is used mainly in urban areas where the spacing is short and the supports are close. All aluminium conductors are made up of one or more strands of aluminium wire depending on the end usage. AAC is also used extensively in coastal regions because it has a high degree of corrosion resistance.

Standard:

ASTM - B 230, ASTM - B 231, TS IEC 1089, DIN48201, BS 215, 

Construction:

Conductor: Hard drawn aluminium conductor as per EN 60889 Type AL1 according to BS 215 

This bare concentric-lay stranded conductor is constructed with a straight round central wire surrounded with one or more layers of helically laid wires.These conductors are also manufactured as compact conductors if required.

Technical parameters:

IEC 1089 Standard

Area mm2Number of wiresDiameterLinearMass kg/kmRated Strength kND.C Resistance Ω/km
Wire mmConductor mm
1071.354.0527.41.952.8633
1671.715.1243.83.041.7896
2572.136.4068.44.501.1453
4072.708.09109.46.800.7158
6373.3910.20172.310.390.4545
100192.5912.90274.817.000.2877
125192.8914.50343.621.250.2302
160193.2716.40439.826.400.1798
200193.6618.30549.732.000.1439
250194.0920.50687.140.000.1151
315373.2923.00867.951.970.0916
400373.7126.001102.064.000.0721
450373.9427.501239.872.000.0641
500374.1529.001377.680.000.0577
560374.3930.701542.989.600.0515
630613.6332.601738.3100.800.0458
710613.8534.601959.1113.600.0407
800614.0936.802207.4128.000.0361
900614.3339.002483.3144.000.0321
1000614.5741.102759.2160.000.0289
1120913.9643.503093.5179.200.0258
1250914.1846.003452.6200.000.0231
1400914.4348.703866.9224.000.0207
1500914.5850.404143.1240.000.0193

ASTM - B 230 &ASTM - B 231 Standard

Code WordSize (AWG Or Kcmil)StrandingDiameterCross-Sectional Area (Sq. Ins.)Weight Per 1000 Ft. (Lbs.)Rated Strength (Lbs.)Allowable Ampacity
  No. Of WiresClassIndividual Wires Complete Cable    
Peachbell67A0.06120.1840.020625563103
Rose47A0.07720.2320.032839881138
Iris27AA,A0.09740.2920.0522621350185
Pansy17AA0.10930.3280.0657781640214
Poppy1/07AA,A0.12280.3680.0829991990247
Aster2/07AA,A0.13790.4140.10451252510286
Phlox3/07AA,A0.15480.4640.13171573040331
Oxlip4/07AA,A0.17390.5220.16631983830383
Sneezewort2507AA0.1890.5670.19642344520425
Valerian25019A0.11470.5740.19632344660426
Daisy266.87AA0.19520.5860.20952504830443
Laurel266.819A0.11850.5920.20952504970444
Peony30019A0.12570.6280.23582815480478
Tulip336.419A0.13310.6650.26443156150513
Daffodil35019A0.13570.6790.27483286390526
Canna397.519AA,A0.14460.7230.3123737110570
Goldentuft45019AA0.15390.7690.35344227890616
Cosmos47719AA0.15840.7920.37444478690639
Syringa47737A0.11350.7950.37444478690639
Zinna50019AA0.11620.8110.39264698760658
Hyacinth50037AA0.11620.8140.39244699110658
Dahlia556.519AA0.17110.8560.43695229750703
Mistletoe556.537AA0.12260.8580.43685229940704
Meadowsweet60037AA0.12730.8910.470956210700738
Orchid63637AA,A0.13110.9180.499559611400765
Heuchera65037AA0.13250.9280.510260911600775
Verbena70037AA0.13750.9630.549465612500812
Flag70061A0.10710.9640.549565612900812

BS 215Standard

CODENominal Aluminum AreaStranding: No.and Nominal Diameter of WiresApprox Overall DiameterCalculated D.C Resistance at 20°C(Max)Approx Weight of ConductorBreaking LoadStandard Packing LengthDrum SizeApprox Cross Weight
 SqmmNo./mmmmohm/KmKg/KmKNMetre±10% KG
MIDGE227/2.066.181.227643.992000D-7175
ANT507/3.109.30.54191458.282000D-9350
FLY607/3.4010.20.45051749.92000D-9410
WASP1007/4.3913.170.2702290162000D-11680
HORNET15019/3.2516.250.182543425.72000D-141020
CHAFER20019/3.7818.90.134958732.42000D-161380
COCKROACH25019/4.2221.10.108373140.42000D-181700
BUTTERFLY30019/4.6523.250.0891688848.752000D-182020
CENTIPEDE40037/3.7826.460.064114563.12000D-192610

DIN48201 Standard

Conductor AreaNominal Aluminum Area91/2.96Approx Overall DiameterCalculated D.C Resistance at 20°C(Max)Approx Weight of ConductorBreaking LoadStandard Packing LengthDrum SizeApprox Cross Weight
SqmmSqmmNo./mmmmohm/KmKg/KmKNMetre±10% KG
1615.897/1.705.11.8017442.842000D-7130
2524.257/2.106.31.1806674.172000D-8180
3534.467/2.507.50.8332945.742000D-8240
5049.487/3.0090.57861357.952000D-9330
5048.3619/1.8090.59481338.442000D-9330
7065.8219/2.1010.50.43718111.282000D-10425
9593.2719/2.5012.50.308425615.652000D-12625
12011719/2.80140.245932218.742000D-12755
150147.137/2.2515.70.19640625.212000D-14965
185181.637/2.5017.50.155850130.462000D-161210
240242.561/2.2520.20.119267039.392000D-181580
300299.461/2.5022.50.0965182747.582000D-181890
400400.161/2.89260.07222110560.722000D-192530
500499.861/3.2329.10.05782138174.562000D-213180
625626.291/2.9632.60.04625173395.062000D-233970
800802.191/3.3536.80.036112219118.261000D-212640
1000999.191/3.7441.10.028792766145.631000D-213190
  • Galvanized Steel Wire (Stranded)
  • ACSR (Aluminium Conductor Steel Reinforced)
  • AAAC(All Aluminum Alloy Conductor)